ITC – VA-6000BC DC Power Supply and Battery Charger
DETAILS:
ITC – VA-6000BC DC Power Supply and Battery Charger
Descriptions:
VA-6000BC is mainly used in VA-6000 system to provide stable and reliable spare DC power when there is no AC power supply.
Features:
- Select charging mode automatically.
- Storage battery failure, overvoltage, over-temperature and overtime charging detection.
- Automatic temperature control fan and overheating protection.
- Storage battery can be changed, will not be influenced by the change of AC power supply.
Basic Functions:
- Build-in battery charge management and monitoring circuit. When connected to AC power, DC 24V will be off automatically.
- Storage battery adopts two DC 24V lead-acid batteries or one DC 24V lead-acid battery.
- Selecting charging mode automatically, to ensure safety charging and service life: pre-charge->constant current->trickle charge.
- High charging efficiency and restore efficiency. Storage battery fault detection, overvoltage detection, over-temperature detection and overtime charging detection.
- Being suitable for multiple volumetric battery <=200Ah.
- Dual internet interfaces, can realize hand in hand connection.
Specifications:
| Model | VA-6000BC |
| AC Power | |
| Power Supply | ~ 220V-240V 50/60Hz |
| Maximum Current | 1.5A |
| Fuse | 250V/2A, low speed type |
| DC Power Output | |
| Power Supply | 24V storage battery |
| Maximum Current | 50A each line |
| Charging | |
| Maximum charging current | 10A, adjustable |
| Heat dissipation | Temperature fan, forced-style |
| Machinery Index | |
| Size(L x W x D) | 484 x 88 x 447mm (19inch, 2U) |
| Weight | About 7.5kg |
| Mounting | Desktop or 19 inch cabinet |
| Color | Black |
| Enviroment Requirement | |
| Operation Temperature | +5℃ ~ +40℃ |
| Storage Temperature | -20℃~ +70℃ |
| Relative Temperature | <95%, (No condensation) |
VA-6000BC Front Panel <<
Connectors
1 Location hole.
2 AC power indicator light:
(1) Off – Charger stops work, storage battery DC supply is still on.
(2) Green – AC supply normal.
3 Storage battery connection status indicator light:
(1) Off – Storage battery connection normal.
(2) Yellow – Storage battery connection off or battery failure.
4 Charging status indicator light:
(1) Off – Charger is not charging the storage battery.
(2) Yellow – Charger is not charging the storage battery.
5 Charging status indicator light:
(1) Off – Voltage normal.
(2) Yellow – Over voltage, charging will be stopped automatically to protect the storage battery.
6 Storage battery output under voltage indicator light:
(1) Off – Voltage normal:
(2) Yellow – Under voltage. This case happens when using dead storage battery for the first time, user need to change a new storage battery.
7 General working status indicator light of charger:
(1) Off – Charger working normal.
(2) Yellow – Charger fault, other failure state will happen at the same time, such as, storage battery is not connected, temperature sensor is not connected and etc.